Circuit Breaker Testing Device

Сircuit Breaker Testing Device DTE-14M

Purpose

Сircuit Breaker Testing Device DTE-14M (High-Current Circuit Breaker Test Device)

The DTE-14M Primary Injection Test Set is a powerful circuit breaker test device designed for testing and verifying the time–current characteristics of AC circuit breakers in the extended range of 50 A to 14,000 A. It measures and records operating time and current, making it essential for testing heavy-duty breakers, protective relays, fuses, and current transformers.

Main Applications

  • Circuit breaker testing (time–current characteristics up to 14 kA).
  • Primary current injection testing and certification of protective and measuring CTs.
  • Relay calibration and adjustment (overcurrent and thermal relays for industrial use).
  • High-power fuse testing and verification.
  • Use as an adjustable AC current source up to 14 kA for laboratory and field tests.

Key Features

  • Mounted on a transport trolley – easy relocation and simplified operation at test sites.
  • Full galvanic isolation of output circuits from the supply ensures operator safety.
  • Wide testing range: breakers, transformers, relays, and fuses up to 14,000 A.
  • Extended capacity compared to DTE-3M, DTE-6M, and DTE-10M.

Price on request.
Contact us to buy the DTE-14M Primary Injection Test Set directly from the manufacturer and get delivery details.

Technical specifications

*Supply Voltage, V400 ±5%
Supply Network Frequency, Hz50 ±1%
Maximum Voltage on Output Buses, V3.5
Maximum Current on Output Buses (RMS), A15400
Maximum Power Consumption DTE-14M, kVA110
**True RMS Measurement and Registration Range of Output Current, A, from 10% (or at least 50 A) to 100% of the selected range with measurement error less than 3%50 – 15400
Measurement and Registration Range of Output Current Duration, sec, with measurement error less than 1.5%0.01 – 9999
Threshold of Power Transformer Overheat Protection, °C96 ±10%
Overall Dimensions of Control Unit BU-14, mm300×250×135
Overall Dimensions of Current Amplifier Unit BPS-14, mm480×250×320
Overall Dimensions of Transport Cart, mm420×220×780
Mass of Control Unit BU-14, kg, max3.6
Mass of Current Amplifier Unit BPS-14, kg, max54
Mass of Current Sensor DS-14, kg, max4
Mass of Transport Cart, kg, max12
Average Service Life of the Device, years10

* Possible DTE-14M power voltage is 230V, wherein the power output would three times decrease. (Maximum output current – 9kA).

** The technical characteristics correspond to the given values ​​when operating the device complete with a single-phase voltage regulator (SVR).

Device operating conditions

Environment temperature range-5 °C — +35°C.
Relative air humidity at +25°C≤85%.
Atmospheric pressure, mm Hg630—800

 
You can see the 3D model of the device at this link

Gallery

Scroll to Top